Internet Payment services are being enhanced. Receipt downloads are temporarily unavailable. For receipt requests, email SCDF_CSC@scdf.gov.sg with your SCDF reference number. Our team will assist you. We apologise for any inconvenience and thank you.

W.e.f. 1 Apr 2024 onwards, refresher training for Fire Station Emergency Medical Technicians will be enhanced and the In Camp Training period will be extended from 19 to 23 days. Please check with your Deputy Commander Fire Station or unit for more info.

W.e.f. 1 Jul 2024, SCDF will change its sender ID for NS Mobilisation matters from “91449746” to “80709995”. This follows the gov.sg SMS Sender ID announcement on 13 Jun 2024 and aims to help recipients recognise and authenticate SMSes from SCDF.

Please be informed that Bukit Batok Fire Station will not be hosting the weekly Saturday Fire Station Open House from 30 Sep 2023 to Feb 2025. Please refer to the list of other Fire Stations that are available for visits.

1

/

4

Search CPFPRTS
Include in Search
Clear All

Please enter a keyword to search

3.15.1 General

Materials used in the construction of station elements shall comply with the provisions stated under this Chapter in addition to the performance requirements such as for fire resistance stipulated in other relevant Chapters.

3.15.2 Intumescent paint

Intumescent paint is allowed to be used for protection of structural steel members of all stations provided all of the following requirements are complied with:

a. The paint shall be of a proprietary system that has been demonstrated to achieve the fire resistance performance as required in BS 476: Part 20/ 21 or its equivalent, together with the specified weathering tests as specified in the BS 8202: Part 2.

b. Coating of intumescent paint onto structural steels, and subsequent maintenance shall conform to BS 8202: Part 2. Fire test for fire resistance performance shall be conducted on the specimens after the weather tests. The fire resistance rating of the tested specimen shall not diminish more than 25%, post-weathering tests.

c. A signage depicting the below minimum information shall be affixed at a conspicuous location:

(1) Name of supplier

(2) Fire resistance rating of the intumescent paint

(3) Date of painting

(4) Expected date of re-painting

(5) Caution note: “Caution – No other paint/ coating shall be applied to the surfaces of the structural steel members protected by the intumescent paint system”

3.15.3 Flame retardant chemicals

Flame retardant chemicals, intended for upgrading of fire resistance rating of any combustible material, shall not be allowed to improve the required fire resistance.

3.15.4 Elements of structure

All elements of structure shall be constructed of non-combustible materials in addition to the relevant provisions as follows:

a. Cl.3.3 for fire resistance of elements of structure

b. Cl.3.5.1 & Cl.3.5.3 for external walls,

c. Cl.3.6.1 Cl.3.6.5 for separating walls,

d. Cl.3.7.1 Cl.3.7.5 for compartment walls and compartment floors,

e. Cl.3.8.2Cl.3.8.2Cl.3.8.4Cl.3.8.7c.Cl.3.8.8,Cl.3.8.9a. for protected shafts.

3.15.5 Protection of openings

Materials used for the protection of openings shall comply with the relevant provisions of Cl.3.9 of this Code for protection of openings.

3.15.6 Exit staircases

Exit staircases shall be constructed of non-combustible materials to comply with the provisions of Cl.3.10.1.

3.15.7 Raised floors

Materials used for the construction of raised floors shall comply with the provisions of Cl.3.11.7a. and Cl.3.11.7e..

3.15.8 Ceiling supports

Materials used for construction of ceiling supports shall comply with the provisions of Cl.3.11.8a..

3.15.9 Fire stopping

Materials used for fire stopping shall comply with the relevant provisions of Cl.3.12.2 and Cl.3.12.3.

3.15.10 Roofs

Materials used for roof construction shall comply with the provisions of Cl.3.14.1.

3.15.11 Non-load bearing walls, partitions, claddings/ wall panels, false ceilings, balustrades and railings

Internal non-load bearing walls, partitions, claddings/ wall panels, false ceiling, balustrades, and railings in stations, including the materials for surface finishes, shall be constructed of non-combustible materials.

Exception: Wall finishes in the form of thin sheets of at most 1mm thickness mounted on non-combustible substrate in commercial space where sprinkler protection is provided.

3.15.12 Materials containing plastics

Composite panels and sandwich panels which has non-combustible covering but consist of plastic or combustible core are prohibited.

3.15.13 PVC pipes

PVC pipes are prohibited in underground stations, except for:

a. Encased PVC pipes in concrete;

b. PVC pipe sleeves in structure; and

c. Condensate drain pipes for air-conditioning units.

3.15.14 Fire-rated glass

Fire-rated glass if used as walls and doors for fire compartmentation of shops, shall comply with the following:

a. the walls and doors shall have the necessary fire resistance, including insulation, when subject to test under BS 476: Part 20-23; and

b. the walls and doors shall meet the requirement of Class A for Impact Performance when tested under BS 6206 and EN 12600 or AS 2208.

3.15.15 Walls finishes

Use of plastic materials as vertical screening/ divider of telecommunication equipment at non-habitable open-to-sky roof is permitted, provided the materials meet at least Class 2 rating classified under BS 476: Part 7 or equivalent.