Internet Payment services are being enhanced. Receipt downloads are temporarily unavailable. For receipt requests, email SCDF_CSC@scdf.gov.sg with your SCDF reference number. Our team will assist you. We apologise for any inconvenience and thank you.

W.e.f. 1 Apr 2024 onwards, refresher training for Fire Station Emergency Medical Technicians will be enhanced and the In Camp Training period will be extended from 19 to 23 days. Please check with your Deputy Commander Fire Station or unit for more info.

W.e.f. 1 Jul 2024, SCDF will change its sender ID for NS Mobilisation matters from “91449746” to “80709995”. This follows the gov.sg SMS Sender ID announcement on 13 Jun 2024 and aims to help recipients recognise and authenticate SMSes from SCDF.

Please be informed that Bukit Batok Fire Station will not be hosting the weekly Saturday Fire Station Open House from 30 Sep 2023 to Feb 2025. Please refer to the list of other Fire Stations that are available for visits.

1

/

4

Search CPFPRTS
Include in Search
Clear All

Please enter a keyword to search

6.7.1 Equipment, fixtures, and fittings

The following equipment, fixtures, and fittings for the fire protection systems shall be painted in red. For those equipment, fixtures, and fittings not listed below, the colour scheme shall be in accordance with that specified in the relevant codes of practice.

a. Fire sprinkler system

(1) Fire pump & control panel

(2) Breeching inlet (excluding breeching inlet cabinet/ enclosure)

(3) Sprinkler control valve

(4) Sprinkler water proofing system/device

b. Electrical fire alarm system

(1) Main fire alarm panel/ cabinet

(2) Sub fire alarm panel/ cabinet

(3) Manual alarm call point

(4) Visual alarm light housing

(Note: fire alarm bell need not be in red)

c. Private fire hydrant

(1) Wet pillar hydrant (with yellow band in accordance with SS 575)

(2) Dry pillar hydrant (whole hydrant in yellow)

d. Dry rising mains

(1) Fire pump & control panel

(2) Breeching inlet (excluding breeching inlet cabinet/ enclosure)

(3) Dry riser breeching inlet in yellow

(4) Landing valve (except dry landing valve to be in yellow)

(5) Rising mains pipe

(6) Standby hose cabinet/ enclosure

e. Hose reel system

(1) Hose reel pump & control panel

(2) Hose reel drum (excluding cabinet/enclosure)

f. Total flooding fire extinguishing system

Breathing apparatus cabinet/ enclosure

g. Emergency Voice Communication System

Handset/ cabinet/ enclosure

h. Fire extinguisher

Housing cabinet/ enclosure

(Note: Alternatively, red graphic signage or red wordings “Fire Extinguisher” of minimum size 20mm shall be provided.)

6.7.2 Pipework, conduits, trunkings, and cable trays

For fire protection systems pipework/ conduits/ trunkings/ cable trays which are not required to be painted in red, red colour bands of width not less than 20mm and labelling shall be provided at an interval of not more than 6m apart.

6.7.3 Graphical symbols

Graphical symbols to depict fire safety equipment are allowed for use in stations provided the signs comply with SS 508. Either graphic or text format can be used for the design of the signage. Table 6.7.3 shows the different sizes of the graphical symbol with respect to the viewing distance.