3.12.1 General provision
Openings for pipes, ducts, conduits or cables which pass through any part of a compartment (except for a part which does not serve as a fire resisting barrier) or cavity barrier, shall be:
a. kept as few in number as possible;
b. kept as small as practicable; and
c. all gaps shall be filled with fire-stopping materials.
3.12.2 Fire-stopping
Materials for fire stopping shall have the necessary fire resistance when tested to BS 476: Part 20 or other acceptable standards.
3.12.3 Materials for fire-stopping
Suitable fire-stopping materials include:
a. Fire-stopping and sealing systems (including those designed for service penetrations) which have been shown by test to maintain the fire resistance of the wall or other element.
b. Other fire-stopping materials include:
(1) cement mortar;
(2) gypsum-based plaster;
(3) cement or gypsum-based vermiculite/ perlite mixes;
(4) glass fibre, crushed rock, blast furnace slag or ceramic based products (with or without resin binders); and
(5) intumescent mastics.
The method of fire-stopping and choice of materials shall be appropriate to the situation and its application.
Updated 2 Sep 2024