Internet Payment services are being enhanced. Receipt downloads are temporarily unavailable. For receipt requests, email SCDF_CSC@scdf.gov.sg with your SCDF reference number. Our team will assist you. We apologise for any inconvenience and thank you.

W.e.f. 1 Apr 2024 onwards, refresher training for Fire Station Emergency Medical Technicians will be enhanced and the In Camp Training period will be extended from 19 to 23 days. Please check with your Deputy Commander Fire Station or unit for more info.

W.e.f. 1 Jul 2024, SCDF will change its sender ID for NS Mobilisation matters from “91449746” to “80709995”. This follows the gov.sg SMS Sender ID announcement on 13 Jun 2024 and aims to help recipients recognise and authenticate SMSes from SCDF.

Please be informed that Bukit Batok Fire Station will not be hosting the weekly Saturday Fire Station Open House from 30 Sep 2023 to Feb 2025. Please refer to the list of other Fire Stations that are available for visits.

1

/

4

Search Fire Code
Include in Search
Clear All

Please enter a keyword to search

CLAUSE 7.5 - REDUNDANCY FOR MECHANICAL VENTILATION AND PRESSURISATION SYSTEMS

7.5.1 Provision

a. Powered system

A standby fan (N+1) shall be provided for each of the following systems, such that in the event one of the duty fans fails or taken out of service, the standby fan shall be automatically activated to meet the required ventilation rate. 

(1) mechanical ventilation systems for: 

(a) smoke-free/ fire lift lobbies;

(b) exit staircases; and

(c) essential rooms (e.g., sprinkler/ wet riser/ hydrant/ hose  reel pump room, standby generator room, FCC, etc.).

(2) engineered smoke control systems; 

(3) car park smoke purging systems*; and 

(4) pressurisation systems for smoke-free/ fire lift lobbies, exit staircase and hotel internal guestroom corridor.

Note * redundancy (N+1) achieved by having at least 2 zones for ductless system in operation, in which N+1 fans for each zone is not required. 

b. Non-powered system

Where automatic smoke ventilators are used as part of the smoke control system, there shall be at least 10% redundancy on the quantities of ventilators and shall be located such that they are not affected by the wind. The quantity of the redundant ventilators shall be round up to whole numbers, based on the largest size of the ventilators used.

Diagram 7.1.13c.(1) - 1 : Unprotected opening perpendicular to the kitchen exhaust duct

Diagram 7.1.13c.(1) - 1 : Unprotected opening perpendicular to the kitchen exhaust duct

Diagram 7.1.13c.(1) - 2 : Unprotected opening parallel to the kitchen exhaust duct

Diagram 7.1.13c.(1) - 2 : Unprotected opening parallel to the kitchen exhaust duct

Diagram 7.1.13c.(2) : Fire resistance construction for kitchen exhaust duct

Diagram 7.1.13c.(2) : Fire resistance construction for kitchen exhaust duct

Diagram 7.1.13c.(3) : Installation of non-fire-rated kitchen exhaust duct above LPG cylinders

Diagram 7.1.13c.(3) : Installation of non-fire-rated kitchen exhaust duct above LPG cylinders

Diagram 7.1.13c.(4) : Installation of non-fire-rated kitchen exhaust duct in close proximity to LPG cylinders and vapouriser

Diagram 7.1.13c.(4) : Installation of non-fire-rated kitchen exhaust duct in close proximity to LPG cylinders and vapouriser

Diagram 7.4.4e.(4) - 1 & 2 : Wiring arrangement of jet fan system

Diagram 7.4.4e.(4) - 1 : Wiring arrangement of jet fan system

Diagram 7.4.4e.(4) - 2 : Wiring arrangement of jet fan system


Updated 2 Sep 2024