A door recess on SS or S/C SS external wall, to accommodate the protrusion of the door handle when the SS door is fully open, shall be provided. Refer to FIGURE 2.10.

a. The dimensions shall not be larger than 160mm (length) x 80mm (height) x 40mm (depth) for SS or S/C SS wall of minimum 300mm thickness and shall accommodate the door handle adequately.

b. The clear spacing between the SS door handle recess and the external socket outlet/ other fixtures or internal fixtures shall be at least 300mm apart.