sg-crest
Hotlines
  • 995

    Fire Engine / Ambulance

  • 1777

    Non-Emergency Ambulance

  • Fire Hazard Reporting

    1800 280 0000

  • General Enquiries

    1800 286 5555

  • 995

    Fire Engine / Ambulance

  • 1777

    Non-Emergency Ambulance

Legend: Explanations & Illustrations Rationale Note Figures & Tables Revision history

Clause 1.4 DEFINITIONS

In this Code, unless the context otherwise requires, the following definitions will apply.

1.4.1 Accessible floor area

“Accessible floor area” refers to the total floor area of all covered spaces within a station, including service ducts, lift shafts, toilets, staircases, areas occupied by fixed/ moveable furniture/ equipment/ facilities, and any open-to-sky habitable areas above or below the first storey of the station.

1.4.2 Aboveground station

“Aboveground station” refers to a station with its trainway located at or aboveground level.

1.4.3 Aboveground trainway

“Aboveground trainway” refers to a portion of the guideway supported by elevated structure, ground level structure, embankment, or cut slope.

1.4.4 Ancillary area

“Ancillary area” refers to the non-public areas used to house or contain operating, maintenance, or support equipment and functions.

1.4.5 Area of compartment/ room/ space

“Area of compartment/ room/ space” refers to the total area of any compartment/ room/ space bounded by the inner finished surfaces of the walls that form the compartment/ room/ space. Where there is no enclosing wall on any one side, the area of the compartment/ room/ space shall be measured by the outermost edge of the floor on that side.

1.4.6 Area of refuge

“Area of refuge” refers to an area within a station or in an adjoining station where evacuees can temporarily take refuge, in lieu of the requirement for adequate exit staircase provision. It shall be adequately separated from the rest of the station or adjoining station by fire-resisting construction and connected via an external corridor or open-sided linkway. The area of refuge shall be always accessible.

1.4.7 Area of roof

“Area of roof” refers to the visible roof area on a plane parallel to the pitch of the roof.

1.4.8 Area of station

“Area of station” refers to the total area of that station bounded by the inner finished surfaces of the enclosing walls. Where there is no enclosing wall on any one side, the area of station shall be measured by the outermost edge of the floor on that side.

1.4.9 Atrium

Atrium” refers to a large open space within a station created by an opening or a series of openings in floor assemblies, thus connecting two or more storeys. An atrium is covered at the top and is used for purposes other than those associated with small shafts e.g. stairs, elevators, and various services. The sides of the atrium can be open to all floors, to some floors, or closed to all or some floors by non-rated or rated fire-resistance construction.

1.4.10 Authority having jurisdiction

“Authority having jurisdiction” refers to non-SCDF local entities, which may include an organisation, office, or individual responsible for enforcing the requirement of a code, standard, or for approving equipment, materials, an installation, or a procedure.

1.4.11 Backlayering

“Backlayering” refers to the reversal of movement of smoke and hot gases counter to the direction of the ventilation airflow.

1.4.12 Basement storey

“Basement storey” refers to a storey of a station for which at least half the storey height is below the ground level, and which also adjoins its perimeter walls for at least half the length of such walls.

a. Exception 1:

Under-Platform Services Ducts (UPSD) and cable chambers conforming with Cl.2.2.4e. and not exceeding 2m measured from finished floor level to ceiling height shall not be considered as a basement in a transit station. The UPSD and cable chambers shall only house cables and services serving the station.

b. Exception 2:

(1) Extended landings that connect transfer exit staircases, ventilation shafts, lift and staircase landings shall not be considered a basement storey in a transit station.

(2) The extended staircase landings shall not be wider than the width of the exit staircase (to prevent other usage i.e. storage).

(3) The ventilation shafts shall not contain mechanical and electrical equipment and cables, other than those serving the shaft itself.

1.4.13 Boundary

“Boundary” refers to the border demarcating the area surrounding the station, and where applicable (in determining the relevant boundary), it includes the imaginary extension of the border up to the centre of an abutting public street, canal, or river.

1.4.14 Buffer areas

“Buffer areas” refer to unenclosed corridors located alongside train-ways beyond the ends of platform screen doors and are inaccessible to the public during normal operation hours. Where buffer areas are designated as part of egress for passengers, they shall be made accessible via the release of electromagnetic/ electromechanical device of the access doors at the ends of the platform screen doors during a fire emergency.

1.4.15 Cavity barrier

“Cavity barrier” refers to a fire-rated construction that seals or sub-divides a concealed space. The cavity barrier helps limit the spread of smoke and fire into or within that concealed space.

1.4.16 Ceiling

“Ceiling” refers to a part of a station or trainway that encloses and is exposed overhead in a room, circulation space, or protected shaft. A soffit or rooflight is included as part of its surface but, not the frame of a rooflight.

1.4.17 Circulation space

“Circulation space” refers to the means of access between a room or protected shaft and an exit from the station or compartment. It shall not be used for any commercial activity such as information and reception counter, or areas used for exhibitions.

1.4.18 Compartment

“Compartment” refers to a part of a station or trainway separated from all other parts of the same station or trainway by compartment walls and/ or compartment floors. A roof space above the top storey of a compartment is included in that compartment.

1.4.19 Compartment wall & compartment floor

“Compartment wall” and “compartment floor” refers to walls or floors of fire-rated construction provided for the purpose of dividing a rapid transit station into compartments.

1.4.20 Concealed space/ Cavity

“Concealed space/ Cavity” refers to a space enclosed by elements of a station (including a suspended ceiling or raised floor) or contained within an element. It is not a room, cupboard, circulation space, protected shaft or space within a flue, chute, duct, pipe, or conduit.

1.4.21 Corridor

“Corridor” refers to a passage providing means of access from rooms or spaces to an exit.

1.4.22 Critical velocity

“Critical velocity” refers to the minimum steady-state velocity of ventilation airflow moving towards the fire within a tunnel or passageway that is required to prevent backlayering at the fire site.

1.4.23 Cubical extent

“Cubical extent” refers to the volume of a space within a station or compartment. This excludes protected lift walls, exit staircases, and other accommodation (such as restrooms and locker rooms) which are enclosed with walls having at least 1-hr fire resistance, and openings protected by doors of ½-hr fire resistance fitted with an automatic self-closing device. It shall be measured according to the following dimensions:

a. The inner finished surfaces of the enclosing walls or on any side where there are no enclosing walls a plane extending vertically above the outermost edge of the floor on that side;

b. The upper surface of its lowest floor; and

c. Where a station or compartment extends to a roof, the under surface of the roof or the under surface of the ceiling of the highest storey within the compartment, including space occupied by any other walls, or any unprotected shafts, ducts, or structures within the spaces to be so measured.

1.4.24 Dead-end

“Dead-end” refers to a situation within a space, normally a corridor or lift lobby spaces where exit is only possible from one end, with no possible escape from the other end.

1.4.25 Direct distance

“Direct distance” refers to shortest distance from the most remote point in a room or space, measured within the external enclosures of the room or space to the relevant exits, ignoring internal walls, partitions, and fittings other than the enclosure walls of exit passageways and exit staircases.

1.4.26 Door

“Door” refers to any shutter, cover, or other form of protection to an opening in any wall, floor, or in the structure surrounding a protected shaft regardless of whether the door is constructed of one or more leaves.

1.4.27 Electromagnetic or Electromechanical locking device

“Electromagnetic” or “Electromechanical locking device” refers to a fail-safe device which provides egress access control. In the event of a fire alarm activation, failure of power supply, and/ or any fault in the locking devices/ components, related to the release of locking mechanism, this device shall:

a. automatically unlock doors immediately to facilitate egress and remain so until power supply is restored; and

b. be provided with a means of manual override located within the occupied space, 1.2m above the floor, and within 1.5m of the door jamb.

1.4.28 Element of structure

“Element of structure” refers to:

a. a member forming part of the structural frame of a station, trainway, or any other beam or column but not a member forming part of a roof structure only, or

b. a load-bearing wall or load bearing part of a wall, or

c. a floor, including a compartment floor, other than the lowest floor (in contact with the ground), or

d. a separating wall, or

e. a structure enclosing a protected shaft (protecting structure).

1.4.29 Emergency lighting

“Emergency lighting” refers to lighting provided with a secondary source of power supply to illuminate the exits and spaces within a station.

1.4.30 Engineering analysis

“Engineering analysis” refers to an analysis that evaluates all factors that affect the fire safety of the system. A report of the analysis indicating the proposed method(s) providing a level of fire safety commensurate with this Code shall be submitted.

1.4.31 Enclosed station

“Enclosed station” refers to a station or portion thereof that does not meet the requirements of an open station.

1.4.32 Exit

“Exit” refers to a means of egress from the interior of the station or trainway to an exterior space. An exit is by the use of the following either singly or in combination: exterior door openings, exit staircases, exit ramps, or exit passageways but not including access stairs, aisles, corridor doors, or corridors. In the case of ancillary area and commercial space in stations are present, exit also include door opening directly to the station public area.

1.4.33 Exit access

“Exit access” refers to the portion of a means of escape that leads to an exit. It includes the room and station spaces that people occupy, the doors along the escape routes, lobbies, aisles, passageways, corridors, access stairs, and ramps traversed in order to reach an exit.

1.4.34 Exit access door

“Exit access door” refers to a door which provides access to a room or space excluding a toilet cubicle, bedroom, storeroom, utility room, pantry and the like, or installed across the escape path leading to an exit.

1.4.35 Exit door

“Exit door” refers to a door provided at the doorway of an exit for the passage of people, forming part of the integrity of the exit, including the exterior door opening.

1.4.36 Exit lighting

“Exit lighting” refers to the part of emergency lighting that is provided to illuminate the exits.

1.4.37 Exit passageway

“Exit passageway” refers to the horizontal extension of a vertical exit via exit staircase or a passage leading from a habitable area to the station public area or an open exterior space.

1.4.38 Exit staircase

“Exit staircase” refers to a staircase constructed of non-combustible material and protected from fire (by fire-rated construction or located at the external space) for the purpose of enabling egress to the external space.

1.4.39 External exit staircase

“External exit staircase” refers to an exit staircase located outside the station, open to the external space, and that:

a. is enclosed by parapet walls or railing of not more than 1.1m in height;

b. has at least two adjacent sides or one of its longest sides abutting the external space; and

c. is recessed not more than 3m from the station façade.

1.4.40 External exit passageway

“External exit passageway” refers to an exit passageway that serves as required exit with at least one of its longest sides open to the external space or air well.

1.4.41 External wall finishes

“External wall finishes” refers to materials/ components installed on the station facade for the purpose of providing thermal insulation, weather resistance and/ or to improve the appearance of stations. They can be made of metal, brick/ stone granite, composite materials, etc. It shall include cladding, fins, and any decorative features mounted on the external walls of a station.

1.4.42 External wall (or side of a station)

“External wall (or side of a station)” refers to an outer wall or vertical enclosure. This includes a part of the roof pitched at an angle of 70º or more to the horizontal if that part of the roof adjoins a space within the station to which persons have access.

1.4.43 Firefighting staircase

“Firefighting staircase” refers to an exit staircase that has its enclosure constructed of non-combustible material and shall have a fire resistance of not less than that for the element of structure and designated for use by firefighters.

1.4.44 Fire lift lobby

“Fire lift lobby” refers to a protected and ventilated/ pressurised lobby into which a fire lift opens and from which direct access to a protected staircase can be made for the purpose of firefighting.

1.4.45 Fire resistance

“Fire resistance” refers to the minimum time period during which an element of structure or element of a station/ trainway can be expected to function satisfactorily while subjected to a standard fire test.

1.4.46 Fire stop

“Fire stop” refers to a seal provided to close an imperfection of fit or any joint between elements, components, or construction in a station, which serves to prevent/ limit the passage of smoke and flame through that imperfection or joint.

1.4.47 Guideway

“Guideway” refers to the portion of the transit line within right-of-way fences, outside lines of curbs or shoulders, underground tunnels, cut or fill slopes, ditches, channels and waterways, and including all appertaining structures.

1.4.48 Habitable floor

“Habitable floor” refers to all floors in a station, including the roof level. The roof level can be taken as non-habitable if it is not used for any purpose/ activity other than housing M&E plants/ equipment, e.g. lift motors, fire pumps, generators, fire hose reel pumps, water supply pumps, water tanks, cooling towers, solar photovoltaic panels, supply/ exhaust fans with associated ductwork, air-con condensing units, telecommunication equipment, satellite dishes, public warning sirens, green roofs inaccessible to public and for maintenance access only, etc.

1.4.49 Habitable height

“Habitable height” refers to the height measured from the level of fire engine accessways or fire engine access roads, whichever is the lowest, to the finished floor level of the highest habitable floor.

1.4.50 Heat release rate

“Heat release rate” refers to energy evolved under a given fire scenario expressed as a function of time.

1.4.51 Height of station

Height of station or part of a station refers to the vertical distance measured from the average level of the ground adjoining the outside of the external walls of the station to the level of half the vertical height of the roof of the station or part, or the top of the walls or of the parapet (if any), whichever is higher.

1.4.52 High hazard occupancy

“High hazard occupancy” refers to any occupancy in which the contents or activities include one or more of the following:

a. material with auto-ignition temperature lower than 200ºC, or

b. materials that produce poisonous, noxious fumes, or flammable vapour, or

c. materials that cause explosions, or

d. high hazard occupancies classified under SS CP 52, or

e. highly combustible substances and flammable liquids.

1.4.53 Load bearing wall

“Load bearing wall” refers to a wall that supports any load in addition to its own weight.

1.4.54 Masonry

“Masonry” refers to brick or concrete construction.

1.4.55 Mechanical ventilation

“Mechanical ventilation” refers to any system that uses mechanical means such as ventilation fan, to introduce outdoor air to a space when natural ventilation mode cannot be achieved during normal and fire emergency situations. This includes supply ventilation, exhaust ventilation, pressurisation, smoke purging, mechanical engineered smoke control systems, balanced systems that consist of both supply and exhaust ventilations, etc.

1.4.56 Non-combustible material

“Non-combustible material” refers to any material which neither burns nor gives off flammable vapour in sufficient quantity to ignite when subjected to the test for combustibility prescribed in BS 476 Part 4, and includes materials of limited combustibility, such as:

a. any material of density 300 kg/m3 or more, which when tested in accordance with BS 476: Part 11, does not flame, and the rise in temperature on the furnace thermocouple is not more than 20°C;

b. any material with a non-combustible core at least 8mm thick having combustible facings (on one or both sides) not more than 0.5mm thick; and

c. any material of density less than 300 kg/m3, which when tested in accordance with BS 476: Part 11,

(1) does not flame for more than 10 sec;

(2) the rise in temperature on the centre (specimen) thermocouple is not more than 35°C; and

(3) the rise in temperature on the furnace thermocouple is not more than 25°C.

1.4.57 Non-load bearing wall

“Non-load bearing wall” refers to a wall that supports no load other than its own weight.

1.4.58 Non-transit occupancy

“Non-transit occupancy” refers to an occupancy not related to the operation of rapid transit systems.

1.4.59 Notional boundary

“Notional boundary” refers to an imaginary boundary which exists at equal distance between buildings/ stations on the same site, or the centre of the width of a public road/ drain/ sewer reserve, provided that the boundary is fronting the respective reserves.

1.4.60 Occupant load

“Occupant load” to a station, or part thereof, refers to the total number of persons that can occupy such a station, or part thereof, at any one time. The “occupant load” shall be determined via the floor area(s) available for occupant based on the appropriate areas per person as stated in Table 1.4.60.

1.4.61 Open station

“Open station” refers to a station that is exposed to the atmosphere where heat and smoke from a train fire are allowed to disperse directly into the atmosphere.

1.4.62 Operation Control Centre (OCC)

“Operation Control Centre (OCC)” refers to a room where the transit system operator controls and coordinates the system-wide movement of passengers and trains. It is here from which communication is maintained with supervisory and operating personnel and with participating agencies when required.

1.4.63 Passenger Service Centre (PSC)

“Passenger Service Centre (PSC)” refers to the room located in a station where communication with the OCC, trains, passengers, and members of the public can be conducted.

1.4.64 Permitted limit of unprotected area

“Permitted limit of unprotected area” refers to the maximum aggregate of unprotected areas in any side or external wall of a station or compartment.

1.4.65 Point of safety

“Point of safety” refers to an enclosed fire exit that leads to a safe location outside the structure, an at-grade point beyond any enclosing structure, or another area that affords adequate protection for passengers.

1.4.66 Pressurisation

“Pressurisation” refers to a mechanical ventilation system that introduce positive differential pressure to a space/ room to prevent smoke ingress during a fire emergency.

1.4.67 Protected shaft

“Protected shaft” refers to an exit staircase, exit passageway, lift, chute, duct, or other shaft which enables persons, things, or air to pass from one compartment to another.

1.4.68 Protecting structure

“Protecting structure” refers to a wall, floor, or other part of the station or trainway which encloses a protected shaft. It is not:

a. A wall which also forms part of an external wall, separating wall or compartment wall, or

b. A floor which is also a compartment floor, or a floor laid directly on the ground, or

c. A roof.

1.4.69 Public area

“Public area” refers to any part of the station normally accessible by members of the public. It includes pedestrian linkways connected to the station.

1.4.70 Railway

“Railway” means a network or system of fixed horizontal rails, tracks, grooves, or other guideway on, under, or above the ground along which a train moves or runs and includes all tunnels, viaducts, bridges, crossings, stabling yards, depots, stations, and other infrastructures constructed or intended to be constructed for any railway and any extensions thereto.

1.4.71 Rapid Transit System (RTS)

“Rapid Transit System (RTS)” means any railway line, or a combination of 2 or more railway lines, and any part thereof comprised in that line, or those lines set up under this Act (Rapid Transit Systems) to meet the transport requirements of the public and includes the Mass Rapid Transit system set up under the repealed Act (Rapid Transit Systems).

1.4.72 Relevant boundary

“Relevant boundary” refers to a boundary in relation to a side or external wall of a station/ building or compartment, including a notional boundary.

1.4.73 Roof light

“Roof light” refers to any element in a roof intended to admit daylight.

1.4.74 Room

“Room” refers to an enclosed space though not an enclosed circulation space, protected shaft, or an enclosed space at most 750mm in depth.

1.4.75 Separated part (of a station)

“Separated part (of a station)” refers to a form of compartmentation separated from another part of the same station by a compartment wall which runs full height of the part and is in one continuous plane.

1.4.76 Separating wall

“Separating wall” refers to a wall dividing or portioning adjoining buildings/ stations.

1.4.77 Singapore Civil Defence Force (SCDF)

“Singapore Civil Defence Force (SCDF)” refers to the Commissioner of Singapore Civil Defence Force and includes officers authorised by him generally or specifically to exercise the powers, functions, and duties conferred by the Fire Safety Act.

1.4.78 Smoke-free lobby

“Smoke-free lobby” refers to a lobby located at the entrance to an exit staircase. This exists to help to prevent or minimise the entry of smoke into the staircase.

1.4.79 Station

“Station” refers to a place designated for the purpose of boarding and alighting passengers. This includes public areas, commercial spaces, ancillary area, and trainway associated with the same structure.

a. Stations with multiple transit lines are stations with one or more train platforms and concourse public areas serving different transit lines within a station.

b. Stations with interchange-link are stations provided with direct transfer between transit lines.

c. Stations connected to non-transit occupancy are stations with:

(1) A pedestrian link connected to non-transit occupancies, and/ or

(2) Station entrance integrated with non-transit occupancies.

1.4.80 Station platform

“Station platform” refers to the area of a station used primarily by passengers boarding and alighting trains. See Diagram 1.4.80.

1.4.80

Diagram 1.4.80: Layout of Station Platform

1.4.81 Trades and services

Type of trades and services permitted in station commercial spaces are stated in Table 1.4A.

1.4.82 Trainway

“Trainway” refers to the portion of the guideway where the transit vehicles operate.

1.4.83 Train-peak load

“Train-peak load” refers to the full seating and standing capacities that a train can carry, specified in Table 1.4.83.

1.4.84 Transit station

“Transit station” refers to station accommodating only passengers and employees of the RTS and incidental occupancies in the station.

1.4.85 Underground station

“Underground station” refers to a station with its trainway located in the basement storey.

1.4.86 Unprotected area

“Unprotected areas”, in relation to a side or external wall of a station refers to:

a. a window, door, or other opening; and

b. any part of the external wall which has less than the relevant fire resistance.

1.4.87 Ventilation openings

“Ventilation openings” refer to fixed natural ventilation openings located in external walls for any space, which shall be always unobstructed, and exclude windows or louvres that are openable or operable. Where fixed louvres are used in natural ventilation openings for exit staircases, smoke-free lobbies or exit passageways they shall consist of a single bank of louvres with blade width not exceeding 150mm, with effective ventilation openings calculated based on the free area calculation stated in Diagram 1.4.87.

1.4.88 Vertical exit

“Vertical exit” refers to an exit staircase or exit ramp serving as required exit from one or more storeys above or below ground level.

1.4.89 Wall surface

“Wall surface”, in the context of internal surfaces, refers to the surface of glazing, and any part of the ceiling sloping at an angle of 70º or more to the horizontal. It does not include:

a. door frames and unglazed parts of doors, or

b. window frames and frames in which glazing is fitted, or

c. architraves, cover moulds, picture rails, skirtings, and similar narrow members, or

d. fitted furniture.

diagram-1-4-87

Diagram 1.4.87: Ventilation Opening Size

TABLE 1.4.60 - Occupant Load Factors
Functional SpacesFactor (m2/person)Remarks
Station platform areas0.5 1 
Shops5 
Bicycle kiosk5 
Office10 
Operation Control Centre10 
Passenger Service Centre10 
Store room10 
Bicycle parking area30 
Bicycle parking area30 
Pedistrian linkway/ Concourse*non-simultaneous
Lobby/ corridor/ staircase*non-simultaneous
Toilets*non-simultaneous
Staff room/ Locker room*non-simultaneous
Note:

* - Non-simultaneeous (not considered for occupant load calculation)

1 - For train peak load, it shall include:
  • train fully seated
  • train car standing areas to compute as 4 passengers/m2
For train peak load by train type and car length - refer to Table.1.4.83
TABLE 1.4.83 - Train Peak Load
Train Type Train Car length (m) Number of Train Cars* Train Peak Load
LRT ~12 1 88
2 176
MRT ~19 3 4
450 600
MRT ~23 3 670
4 890
6 1340
8 1780
Note:

* - Train Peak Load for any total train cars not listed here will be multiply/ proportion according to respective train type and car length
TABLE 1.2A: CODES & STANDARDS
Name Description Remarks
SINGAPORE STANDARDS
SS CP 52 CoP for Automatic Fire Sprinkler System  
SS 299 Fire Resistant Cables  
SS 332 Specification for Fire Door  
SS 489 Specification for Fire Shutters  
SS 508 Graphical Symbols - Safety Colours & Safety Signs Formerly SS 217 & SS 364
Pt 1 Design Principles for Safety Signs & Safety Markings
Pt 2 Design Principles for Product Safety Labels
SS 546 CoP for Emergency Voice Communication Systems in Buildings Formerly CP 25
SS 550 CoP for Installation, Operation and Maintenance of Electric Passenger and Goods Lifts Formerly CP 2
SS 551 CoP for Earthing Formerly CP 16
SS 563 CoP for the Design, Installation & Maintenance of Emergency Lighting and Power Supply Systems in Building Formerly CP 19
Pt 1 Emergency lighting
Pt 2 Installation Requirements and Maintenance Procedures
SS 575 CoP for Fire Hydrant, Rising Mains and Hose Reel System Formerly CP 29
SS 578 CoP for the Use and Maintenance of Portable Fire Extinguishers Formerly CP 55
SS 638 Code of Practice for Electrical Installations Formerly CP 5
SS 645 CoP for Installation and Servicing of Electrical Fire Alarm System Formerly CP 10
SS EN 3 Specification for Fire Extinguishers  
SS EN 1992 Design of Concrete Structures Formerly CP 65
Pt 1 General Rules and Rules for Buildings
Pt 2 Concrete Bridges – Design and Detailing Rules
AMERICAN STANDARDS
ANSI American National Standards Institute
A14.3 American National Standard for Ladders - Fixed – Safety Requirements
AUSTRALIAN STANDARDS
AS 2208 Safety Glazing Materials in Buildings
BRITISH STANDARDS
BS 476 Fire Tests on Building Materials and Structures
Pt 4 Non-Combustibility Test for Materials
Pt 5 Method of Test for Ignitability
Pt 6 Method of Test for Fire Propagation for Products
Pt 7 Method of Test to Determine the Classification of the Surface Spread of Flame of Products
Pt 11 Method for Assessing the Heat Emission from Building Materials
Pt 20 Method for Determination of the Fire Resistance of Elements of Construction (General Principles)
Pt 21 Methods for Determination of the Fire Resistance of Load-Bearing Elements of Construction
Pt 22 Method for Determination of the Fire Resistance of Non-Load-Bearing Elements of Construction
Pt 23 Methods for Determination of the Contribution of Components to the Fire Resistance of a Structure
Pt 24 Method for Determination of the Fire Resistance of Ventilation Ducts
BS 1230: Pt 1 Specification for Plasterboard Excluding Materials Submitted to Secondary Operations Replaced by BS EN 520
BS 4514 Specification for Unplasticized PVC Soil and Ventilating Pipes of 82.4mm Minimum Mean Outside Diameter, and Fittings and Accessories of 82.4mm and of Other Sizes
BS 5234 Partitions (including matching linings)  
Pt 2 Specification for Performance Requirements for Strength and Robustness including Methods of Test  
BS 5395: Pt 3 Stairs, Ladders and Walkways. Code of Practice for the Design of Industrial Type Stairs, Permanent Ladders and Walkways  
BS 5499 Fire Safety Signs, Notices and Graphic Symbols
Pt 2 Specification for Performance Requirements for Strength and Robustness including Methods of Test Withdrawn
BS 5588 Fire Precautions in the Design, Construction and Use of Buildings
Pt 5 CoP for Firefighting Stairways and Lifts  
BS 6206 Specification for Impact Performance Requirements for Flat Safety Glass and Safety Plastics for Use in Buildings Replaced by EN 12600
BS 6391 Specification for Non-Percolating Layflat Delivery Hoses and Hose Assemblies for Fire Fighting Purposes  
BS 8202 Coatings for Fire Protection of Building Elements
Pt 2 CoP for the Use of Intumescent Coating Systems to Metallic Substrates for Providing Fire Resistance  
BS EN 1329 Plastics Piping Systems for Soil and Waste Discharge (Low and High Temperature) within the Building Structure
Pt 1 Unplasticized Poly (Vinyl Chloride) (PVC-U) – Specifications for Pipes, Fittings and the Systems
IEC STANDARDS
IEC 60331 Tests for Electric Cables Under Fire Conditions – Circuit Integrity
Pt 25 Procedures and Requirements – Optical Fibre Cables  
IEC 60332 Tests on Electric and Optical Fibre Cables Under Fire Conditions – All Parts  
Pt 1 Test for Vertical Flame Propagation for a Single Insulated Wire or Cable - Apparatus
Pt 3 Test for Vertical Flame Spread of Vertically-Mounted Bunched Wires or Cable - Apparatus  
IEC 61034 Measurement of Smoke Density of Cables Burning Under Defined Conditions  
IEC 60754 Tet on gases Evolved during Combustion of Materials From Cables
Pt 1 Determination of the Halogen Acid Gas Content  
ISO STANDARDS
ISO 1896 Thermal Insulating Asbestos Boards  
Note:

- The Standards stated above are non-exhaustive.

- SCDF shall not be held responsible for the accuracy of the standard titles shown in this table..
TABLE 1.3A: ABBREVIATIONS
Abbreviation Definations
ACMV Air-Conditioning & Mechanical Ventilation
AFA Accessible Floor Area
ANSI American National Standards Institute
AS Australian Standards
BS British Standard
CD Civil Defence
Cl. Clause
CoP Code of Practice
CPFPRTS Code of Practice for Fire Precautions in Rapid Transit Systems
FCC Fire Command Centre
HR Hour
IEC International Electrotechnical Commission
ISO International Organisation for Standardisation
LED Light-Emitting Diode
OCC Operation Control Centre
PSC Passenger Service Centre
PV Photo-Voltaic
PVC Polyvinyl Chloride
PWDs Persons With Disabilities
QP Qualified Person
RTS Rapid Transit System
SCDF Singapore Civil Defence Force
SS Singapore Standard
TV Tunnel Ventilation
TVF Tunnel Ventilation Fan
UPSD Under-Platform Service Ducts
TABLE 1.4A: APPROVED TRADES & SERVICES IN STATIONS
CodeGroupingType
AGeneral24 hours convenience store
MerchandiseMini mart/ provision shop
BClothing & ShoesChildren’s wear/ accessories
Fashion accessories
CHousehold SuppliesHardware/ DIY shop(1)Household ware/ utensils
Home furnishing centre(1)
DOther RetailArts/ antiquesName cards
Bridal saloon/ shopPerfume
Chinese medical hallSports/ golf
ClockTelecommunications
Electrical goodsVideo library/ Cassettes/ CD/ VCD/  Fruits Laser Disc/ DVD
Fruits
EFinancialBank/ auto lobby
FServices
AcupunctureLAN game/ internet café
Child adoption agencyMedical/ dental clinic
Counselling centrePawnshop
Copying and duplicating services Renovation contractor showroom
Fitness centreTherapy/ osteopathy/ chiropractic centre
Hairdressing/ beauty salonToys/ toy collectibles shop
Hand phone repair centreWellness centre/ spa
Internet service providerYoga/ martial arts school
Video games arcade, computer gaming centre, billiard saloon
GFood & Beverages Café(2)Snack bars(2)
Cake/ confectionery/ pastryshop(2)Takeaway food and beverages shop(2)
Fast food kiosk(2)Titbits/ candies/ biscuits
HBicycle parking area(3)Bicycle kiosk(1), (3) with activities confine to bicycle servicing, repairs, cleaning, sale of bicycle accessories and spare parts
Note:

(1) - There shall be no sale or storage of paint, solvent, thinner and bicycle batteries. Charging of bicycle batteries is not allowed in the bicycle parking area or bicycle kiosk.

(2) - For the Food and Beverage outlets, there shall be no open-flame.

(3) - The underground bicycle area is excluded from the 115m2 aggregated size for shop as permitted in Cl.3.2.4c.(2).