sg-crest
Hotlines
  • 995

    Fire Engine / Ambulance

  • 1777

    Non-Emergency Ambulance

  • Fire Hazard Reporting

    1800 280 0000

  • General Enquiries

    1800 286 5555

  • 995

    Fire Engine / Ambulance

  • 1777

    Non-Emergency Ambulance

Legend: Explanations & Illustrations Rationale Note Figures & Tables Revision history

2.5 SPECIAL REQUIREMENTS FOR PERSON WITH DISABILITIES (PWDs)

2.5.1 General

Effective Date: 1 Sep 2024

a. The scope of these requirements on the design and management of transit stations covers the public area of transit stations and excludes RTS depots, ancillary buildings, viaducts, and tunnels. These requirements are intended for the safe evacuation of PWDs during fire emergency.

b. Transit station public areas are designed with barrier-free accessibility under the Building Control Act. The ingress/ egress routes for PWDs shall also be used as evacuation routes for PWDs.

c. Transit stations are of non-combustible construction. The station public areas are segregated from the ancillary areas by fire-rated construction and are designed with emergency ventilation system to provide a tenable environment for evacuation in the event of fire emergency.

d. Passenger lifts in stations are primarily provided for use by PWDs. These lifts that are located in the public area shall be used for the evacuation of PWDs.

e. Management procedures and responsibilities shall be formulated for the evacuation of PWDs in the event of fire.

f. The evacuation route for PWDs in the public areas shall comply with the requirements of the authority having jurisdiction on accessibility  in the Built Environment.

g. The requirements in Section 2.5 do not apply to stations/ areas exempted from barrier-free accessibility compliance, as required by the authority having jurisdiction on accessibility in the built environment.

2.2.4d

Diagram: 2.2.4d. island Platform

 

 

2.2.17c.1

For the fire doors, see hardware and other requirements for doors in Cl.3.9.2.

Sequential door closer shall be provided to both leaves.

Automatic flush bolt shall be provided. See Cl.2.2.17i..

For fire doors, automatic self-closing devices on both door leaves and sequence selector shall be provided.

Diagram 2.2.17c.(1): Measurement of Door Width

 

 

2.2.17e.1

Door shall not encroach into the required width of the landing during its swing

Minimum width of corridor as required  under Cl.2.2.3h., Cl.2.2.4f., and Cl.2.2.8.

Exit doors shall not impede the egress of occupants when such doors are swung open.

Minimum ½ width of corridor as required under Cl.2.2.3h., Cl.2.2.4f., and Cl.2.2.8.

Diagram 2.2.17e.(1): Exit Doors Opening into Exit Staircases and Exit Passageways

Remoteness of Exits

2.2.19a

Diagram 2.2.19a. - 1

Diagram 2.2.19a. - 2

2.2.19a-2One-way escape arrangement

The distance between the two staircases is less than half the length of the maximum overall diagonal dimension of the area

Diagram 2.2.19a. - 3

Two-way escape arrangement

The distance between the two staircases is less than half the length of the maximum overall diagonal dimension of the area

Diagram 2.2.19a. - 4

Diagram 2.2.19a. - 5

Diagram 2.2.19a. - 6

 

2.2.19c

Remoteness of exits is measured along the 1-hr rated corridor with ½ hr fire doors

Diagram 2.2.19c.: Remoteness of Exit

 

 

2.3.2.1

Diagram 2.3.2 – 1

 

2.3.2.2

Diagram 2.3.2 – 2

 

2.4.2.1

Diagram 2.4.2 – 1

 

2.4.2.2

Diagram 2.4.2 – 2

TABLE 2.2.2d.: OCCUPANCY LOAD FOR COMMERCIAL SPACES
FUNTIONAL SPACESOCCUPANCY LOAD (m2/person)
Reception Area3
Lobby/ Corridors*
Fixed Corridors*
Waiting Area/ Visitors Lounge3
Atrium Floor3
Exhibition/ Promotion Area1.5
Shop Floor5
Showroom5
Supermarket/ Bazaar5
Department Store5
Admin. Office10
Toilets/ Staff Rest Room*
Storage30
Mechanical Plant Room30
Classroom1.5

Note:

* - not considered for occupant load calculation

TABLE 2.2.3h.: CAPACITY OF MEANS OF ESCAPE
Type of Means of Escape Capacity (p/m/min) Travel Speed (m/min)
Platforms, corridors, and ramps not more than 4% in slope 80(1) 60
Stairs, escalators, and ramps greater than 4% in slope 60(2) up 15(3)
down 18(3)
Doors and gates(5) 80(4) N/A

Note:

(1) - In calculating the capacity of horizontal means of escape routes with a slope not exceeding 4%, 300mm shall be deducted at each sidewall and 450mm at platform edges.

(2) - Refer to Cl.2.2.3c.(2) with respect to the allowable means of escape contribution for escalators.

(3) - The distance component of travel speed for stairs and stopped escalators is the vertical change in elevation.

(4) - Measurement of door width shall be in accordance with Cl.2.2.17c..

(5) - Capacity for fare collection gates shall be in accordance with Cl.2.2.3i..

TABLE 2.2.4f.: CAPACITY OF EXIT FACILITIES
Type of Means of Escape Capacity (1)

No. of person per unit of width (2)
Exit & corridor doors(3) 80
Staircases 60
Ramps, corridors & exit passageways 100

Note:

(1) - Where a room or space is required to be provided with two exits, each exit shall be of sufficient width to accommodate at least one half the total occupant load.

(2) - In the determination of each exit width, fractions of a unit width less than 250mm shall not be credited. Where 250mm or more are added to one or more full units, half of a unit of width shall be credited. Exit width shall be the clear width of the means of escape.

(3) - Measurement of door width shall be in accordance with Cl.2.2.17c..

  
TABLE 2.2.4g.: TRAVEL DISTANCE
Occupancy Means of escape Maximum travel distance (m)
Sprinkler-protected/ Open-to-sky Non-sprinkler- protected
Commercial One-way 25 15
Two-way 60 45
Ancillary* One-way 30 15
Two-way 75 60
High hazard One-way 20 10
Two-way 35 20

Note:

* See Cl.2.2.4d. for requirements at buffer areas.

In a large floor area without sub-division of rooms, corridors and so forth, the travel distance can adopt the “direct distance” concept as a guide and shall not exceed two-third of the maximum travel distance permitted in this table. Where the large floor area is subdivided into rooms, corridors, etc. the maximum travel distance shall be in accordance with the above table. Furniture, internal partitions and equipment, e.g. air-handling unit, air-con chiller, tunnel ventilation fans, electrical switch board, in rooms can be ignored in determining the direct distance.

 

TABLE 2.2.17l.(2) - 1: PRE-REQUISITES FOR USE OF ELECTROMAGNETIC/ ELECTROMECHANICAL LOCKING DEVICE
Location Approved automatic fire alarm or sprinkler systems Emergency lighting* Manual override device (Emergency Door Release)**

Exit access doors and/ or exit doors in the escape path for the public.

 

Yes Yes Yes

Doors to access essential rooms for fire protection systems, as stipulated under Cl.8.2.7, except those rooms directly accessed from escape path for the public

 

Yes Yes Yes

Exit access door and/ or exit door to rooms not in the escape path for the public.

 

Yes Yes Yes
   

Note:

- Linking of the locking devices through other systems to the station fire alarm system or sprinkler system is not permitted.

- Signage complying with SS 508 shall be installed on the egress side of doors reading “Emergency Exit. Door will automatically unlock in case of fire/ emergency”.

* Manual override devices shall be provided with a minimum level of illuminance in accordance with SS 563

** Activation of manual override device for emergency door release shall automatically and immediately unlock the doors to facilitate egress. The manual override device shall be located within the occupancy space, 1.2m above the finished floor level and within 1.5m of the door jamb. The manual override device shall be readily accessible and clearly identified by a sign that reads “Emergency Door Release”. Any device used by staff for access control to facilitate their day-to-day operations shall not be considered as a substitute for the manual override device. The manual override device, when operated, shall result in direct interruption of power to the lock independent of the control system electronics.


E
TABLE 2.2.17l.(2) - 2: DE-ENERGISE REQUIREMENTS FOR ELECTROMAGNETIC/ ELECTROMECHANICAL LOCKING DEVICE
LocationAny power failure to affected spaces/ areasUnder fire alarm activationAny fault in the locking devices/ components related to the release of locking mechanism*Upon activation of a manually operated switch by authorised personnel manning the PSC, or in the absence of which, at the OCC

Exit access doors and/ or exit doors in the escape path for the public

 

To be released immediately**To be released immediatelyTo be released immediatelyTo be released immediately

Doors to access essential rooms for fire protection systems, as stipulated under Cl.8.2.7, except those rooms directly accessed from escape path for the public

 

Release not requiredTo be released immediatelyRelease not requiredRelease not required

Exit access door and/ or exit door to rooms not in the escape path for the public.

 

Release not requiredRelease not requiredRelease not requiredRelease not required
Note:
 
* Excluding faults on other access control devices such as card readers, override key switches, non-emergency exit buttons, etc.
 
** Electromagnetic/ Electromechanical locking device can be manually re-engaged after it has been released, provided such a device complies with the following:
 
    (1) There is no activation of any fire detection system and it has been visually verified that there is no fire; and
 
    (2) A device to re-engage the Electromagnetic/ Electromechanical locking shall be provided at the PSC or  OCC, if PSC is not available.