Please enter a keyword to search
A1.0 General
In this Annex:
a. “Class 1 aggregate” means foamed slag, pumice, blast furnace slag, pelleted fly ash, crushed brick and burnt clay products (including expanded clay) well-burnt clinker and crushed limestone.
b. “Class 2 aggregate” means flint gravel, granite, and all crushed natural stones other than limestones.
c. Any reference to plaster means:
(1) in the case of an external wall 1m or more from the relevant boundary, plaster applied on the internal face only;
(2) in the case of any other wall, plaster applied on both faces;
(3) if to plaster of a given thickness on the external face of a wall, except in the case of a reference to vermiculite-gypsum plaster, rendering on the external face of the same thickness; and
(4) if to vermiculite-gypsum plaster, vermiculite-gypsum plaster of a mix within the range of 1½ to 2:1 by volume.
d. In the case of a cavity wall, the load is assumed to be on inner leaf only except for fire resistance period of 4-hrs.
e. Any material or type of construction and its method of preparation or application as referred to in the table, shall conform with the relevant provisions of the Building Control Act (Chapter 29) and the relevant Singapore Standard or Singapore Standard Code of Practice. In the absence of the aforementioned Standard or Code of Practice, the relevant British equivalent or other accepted standard or codes of practice shall be applicable.
A2.0 : WALLS
A2.0 : WALLS | ||||||||||||
Construction and Materials | Minimum thickness excluding plaster (in mm) for period of fire resistance of | |||||||||||
Load-bearing | Non-load-bearing | |||||||||||
4 hrs | 3 hrs | 2 hrs | 1½ hrs | 1 hr | ½ hr | 4 hrs | 3 hrs | 2 hrs | 1½ hrs | 1 hr | ½ hr | |
A2.1 -- Mansonry Construction | ||||||||||||
1. Reinforced concrete, minimum concrete cover to main reinforcement of 25mm: | ||||||||||||
(a) Unplastered (to comply with SS EN 1992–1–2) | - | - | - | - | - | - | - | - | - | - | - | - |
(b) 12.5mm cement-sand plaster | 180 | - | 100 | 100 | 75 | 75 | - | - | - | - | - | - |
(c) 12.5mm gypsum-sand plaster | 180 | - | 100 | 100 | 75 | 75 | - | - | - | - | - | - |
(d) 12.5mm vermiculite-gypsum plaster | 125 | - | 75 | 75 | 63 | 63 | - | - | - | - | - | - |
2. No-fines concrete of Class 2 aggregate: | ||||||||||||
(a) 13mm cement-sand plaster | - | - | - | - | - | - | 150 | 150 | 150 | 150 | 150 | 150 |
(b) 13mm gypsum-sand plaster | - | - | - | - | - | - | 150 | 150 | 150 | 150 | 150 | 150 |
(c) 13mm vermiculite-gypsum plaster | - | - | - | - | - | - | 150 | 150 | 150 | 150 | 150 | 150 |
3. Bricks of clay, concrete or sand-lime: | ||||||||||||
(a) Unplastered | 200 | 200 | 100 | 100 | 100 | 100 | 170 | 170 | 100 | 100 | 75 | 75 |
(b) 13mm cement-sand plaster | 200 | 200 | 100 | 100 | 100 | 100 | 170 | 170 | 100 | 100 | 75 | 75 |
(c) 13mm gypsum-sand plaster | 200 | 200 | 100 | 100 | 100 | 100 | 170 | 170 | 100 | 100 | 75 | 75 |
(d) 13mm vermiculite-gypsum or perlite-gypsum* plaster | 100 | - | 100 | 100 | 100 | 100 | 100 | - | 100 | 100 | 75 | 75 |
4. Concrete blocks of Class 1 aggregate: | ||||||||||||
(a) Unplastered | 150 | - | 100 | 100 | 100 | 100 | 150 | - | 75 | 75 | 75 | 50 |
(b) 12.5mm cement-sand plaster | 150 | - | 100 | 100 | 100 | 100 | 150 | - | 75 | 75 | 75 | 50 |
(c) 12.5mm gypsum-sand plaster | 150 | - | 100 | 100 | 100 | 100 | 150 | - | 75 | 75 | 75 | 50 |
(d) 12.5mm vermiculite-gypsum plaster | 100 | - | 100 | 100 | 100 | 100 | 75 | - | 75 | 62 | 50 | 50 |
5. Concrete blocks of Class 2 aggregate: | ||||||||||||
(a) Unplastered | - | - | 100 | 100 | 100 | 100 | 150 | - | 100 | 100 | 75 | 50 |
(b) 12.5mm cement-sand plaster | - | - | 100 | 100 | 100 | 100 | 150 | - | 100 | 100 | 75 | 50 |
(c) 12.5mm gypsum-sand plaster | - | - | 100 | 100 | 100 | 100 | 150 | - | 100 | 100 | 75 | 50 |
(d) 12.5mm vermiculite-gypsum plaster | 100 | - | 100 | 100 | 100 | 100 | 100 | - | 75 | 75 | 75 | 50 |
6. Autoclaved aerated concrete blocks, density 475 - 1200 kg/m3 | 180 | 140 | 100 | 100 | 100 | 100 | 100 | - | 62 | 62 | 50 | 50 |
7. Hollow concrete blocks, one cell in wall thickness, of Class 1 aggregate: | ||||||||||||
(a) Unplastered | - | - | 100 | 100 | 100 | 100 | 150 | - | 100 | 100 | 100 | 75 |
(b) 12.5mm cement-sand plaster | - | - | 100 | 100 | 100 | 100 | 150 | - | 100 | 75 | 75 | 75 |
(c) 12.5mm gypsum-sand plaster | - | - | 100 | 100 | 100 | 100 | 150 | - | 100 | 75 | 75 | 75 |
(d) 12.5mm vermiculite-gypsum plaster | - | - | 100 | 100 | 100 | 100 | 150 | - | 75 | 75 | 62 | 62 |
8. Hollow concrete blocks, one cell in wall thickness, of Class 2 aggregate: | ||||||||||||
(a) Unplastered | - | - | - | - | - | - | 150 | - | 150 | 125 | 125 | 125 |
(b) 12.5mm cement-sand plaster | - | - | - | - | - | - | 150 | - | 150 | 125 | 125 | 100 |
(c) 12.5mm gypsum-sand plaster | - | - | - | - | - | - | 150 | - | 150 | 125 | 125 | 100 |
(d) 12.5mm gypsum-sand plaster | - | - | - | - | - | - | 125 | - | 100 | 100 | 100 | 75 |
9. Cellular clay blocks not less than 50% solid | ||||||||||||
(a) 12.5mm cement-sand plaster | - | - | - | - | - | - | - | - | - | - | 100 | 75 |
(b) 12.5mm gypsum-sand plaster | - | - | - | - | - | - | - | - | - | - | 100 | 75 |
(c) 12.5mm vermiculite-gypsum plaster | - | - | - | - | - | - | 200 | - | 100 | 100 | 100 | 62 |
10. Cavity wall with outer leaf of bricks or blocks of clay, composition, concrete or sand-lime, not less than 100mm thick and; | ||||||||||||
(a) inner leaf of bricks or blocks of clay, composition, concrete or sand lime | 100 | 100 | 100 | 100 | 100 | 100 | 75 | - | 75 | 75 | 75 | 75 |
(b) inner leaf of solid or hollow concrete bricks or blocks of Class 1 aggregate | 100 | 100 | 100 | 100 | 100 | 100 | 75 | - | 75 | 75 | 75 | 75 |
11. Cavity wall with outer leaf of cellular clay blocks as 9 above and inner leaf of autoclaved aerated concrete blocks, density 480-1200 kg/m3 | 150 | 140 | 100 | 100 | 100 | 100 | 75 | 75 | 75 | 75 | 75 | 75 |
Note: * - Perlite-gypsum plaster to clay bricks only |
A2.0 : WALLS | |
Construction and Materials |
Period of Fire Resistance hrs |
A2.2 - Framed and Composite Construction (non-load-bearing) | |
1. Steel frame with external cladding of 16mm rendering on metal lathing and internal lining of autoclaved aerated concrete blocks, density 480-1120 kg/m3 of thickness of – | |
(a) 50mm | 2 |
(b) 62mm | 3 |
(c) 75mm | 4 |
2. Steel frame with external cladding of 100mm concrete blocks and internal lining of 16mm gypsum plaster on metal lathing | 4 |
3. Steel frame with external cladding of 16mm rendering on metal lathing and internal lining of 16mm gypsum plaster on metal lathing | 1 |
4. Steel or timber frame with facings on each side of - | |
(a) metal lathing with cement-sand or gypsum plaster of thickness of- | |
(1) 19mm | 1 |
(2) 12.5mm | ½ |
(b) metal lathing with vermiculite-gypsum or perlite-gypsum plaster of thickness of- | |
(1) 25mm | 2 |
(2) 19mm | 1½ |
(3) 12.5mm | 1 |
(c) 9.5mm plasterboard with gypsum plaster of thickness of 5mm | ½ |
(d) 9.5mm plasterboard with vermiculite-gypsum of thickness of- | |
(1) 25mm | 2 |
(2) 16mm | 1½ |
(3) 10mm | 1 |
(4) 5mm | ½ |
(e) 12.5mm plasterboard | |
(1) unplastered | ½ |
(2) with gypsum plaster of thickness of 12.5mm | 1 |
(f) 12.5mm plasterboard with vermiculite-gypsum plaster of thickness of- | |
(1) 25mm | 2 |
(2) 16mm | 1 ½ |
(3) 10mm | 1 |
(g) 19mm plasterboard (or two layers of 9.5mm fixed to break joint) without finish | 1 |
(h) 19mm plasterboard for two layers of 9.5mm with vermiculite-gypsum plaster of thickness of- | |
(1) 16mm | 2 |
(2) 10mm | 1 ½ |
(i) 12.5mm fibre insulating board with gypsum plaster of thickness of 12.5mm | ½ |
(j) 25mm wood wool slabs with gypsum plaster of thickness of 12.5mm | 1 |
5. Compressed straw slabs in timber frames finished on both faces with gypsum plaster of thickness of 5mm | 1 |
6. Plasterboard 9.5mm cellular core partition- | |
(a) unplastered | ½ |
(b) 12.5mm gypsum plaster | ½ |
(c) 22mm vermiculite-gypsum plaster | 2 |
7. Plasterboard 12.5mm cellular core partition- |
|
(a) unplastered | ½ |
(b) 12.5mm gypsum plaster | 1 |
(c) 16mm vermiculite-gypsum plaster | 2 |
8. Plasterboard 19mm finished on both faces with 16mm gypsum plaster | 1 |
9. Plasterboard 12.5mm bonded with neat gypsum plaster to each side of 19mm plasterboard | 1 |
10. Three layers of 19mm plasterboard bonded with heat gypsum plaster | 2 |
11. Wood wool slab with 12.5mm rendering or plaster of thickness of- | |
(a) 75mm | 2 |
(b) 50mm | 1 |
12. Compressed straw slabs, with 75mm by 12.5mm wood cover strips to joints, of thickness of 50mm | ½ |
Note : * - The presence of a combustible vapour barrier within the thickness of these constructions shall not be regarded as affecting these periods of fire resistance |
A2.0 : WALLS | |
Construction and Materials |
Period of Fire Resistance hrs |
A2.3 - External walls (non-loadbearing) more than 1m from the relevant boundary | |
1. Steel frame with external cladding of non-combustible sheets and internal lining of- | |
(a) 12.5mm cement-sand or gypsum plaster on metal lathing | 4 |
(b) two layers of 9.5mm plasterboard | ½ |
(c) 9.5mm plasterboard finished with gypsum plaster of thickness of 12.5mm | ½ |
(d) 12.5mm plasterboard finished with 5mm gypsum plaster | ½ |
(e) 50mm compressed straw slabs | ½ |
(f) 50mm compressed straw slabs finished with 5mm gypsum plaster | 2 |
2 *Timber frame with external cladding of 10mm cement-sand or cement-lime rendering and internal lining of- | |
(a) 16mm gypsum plaster on metal lathing | 1 |
(b) 9.5mm plasterboard finished with12.5 mm gypsum plaster | 1 |
(c) 12.5mm plasterboard finished with 5mm gypsum plaster | 1 |
(d) 50mm compressed straw slabs | 1 |
(e) aerated concrete blocks | 1 |
(1) 50mm | 3 |
(2) 62mm | 4 |
(3) 75mm | 4 |
(4) 100mm | 4 |
3 Timber frame with external cladding of 100mm clay, concrete or sand-lime bricks of blocks, finished internally with 16mm gypsum plaster on metal lathing | 4 |
4. *Timber frame with external cladding of weather boarding or 9.5 mm plywood and internal lining of- | |
(a) 16mm gypsum plaster on metal lathing | ½ |
(b) 9.5mm plasterboard finished with 12.5mm gypsum plaster | ½ |
(c) 12.5mm plasterboard finished with 5mm gypsum plaster | ½ |
(d) 50mm compressed straw slabs | ½ |
(e) aerated concrete blocks- | |
(1) 50mm | 3 |
(2) 62mm | 4 |
(3) 75mm | 4 |
(4) 100mm | 4 |
Note: * - The presence of a combustible vapour barrier within the thickness of these constructions shall not be regarded as affecting these periods of fire resistance |
A3.0: REINFORCED CONCRETE BEAMS
A3.0: REINFORCED CONCRETE BEAMS | ||||||
Description | Minimum Dimension (mm) of Concrete to give a Fire Resistance of:- | |||||
4 hrs | 3 hrs | 2 hrs | 1 ½ hrs | 1 hr | ½ hr | |
1 Siliceous aggregate concrete: | ||||||
(a) average concrete cover to main reinforcement | 65* | 55* | 45* | 35 | 25 | 15 |
(b) beam width | 280 | 240 | 180 | 140 | 110 | 80 |
2. As (1) with cement or gypsum plaster 15mm thick on light mesh reinforcement | ||||||
(a) average concrete cover to main reinforcement | 50* | 40 | 30 | 20 | 15 | 15 |
(b) beam width | 250 | 210 | 170 | 110 | 85 | 70 |
3. As (1) with vermiculite/ gypsum plaster+ 15mm thick: | ||||||
(a) average concrete cover to main reinforcement | 25 | 15 | 15 | 15 | 15 | 15 |
(b) beam width | 175 | 145 | 125 | 85 | 60 | 60 |
4. Light weight aggregate concrete: | ||||||
(a) average concrete cover to main reinforcement | 50 | 45 | 35 | 30 | 20 | 15 |
(b) beam width | 250 | 200 | 160 | 130 | 100 | 80 |
Note: * - Supplementary reinforcement, to hold the concrete cover in position, may be necessary + - Vermiculite/ gypsum plaster should have a mix ratio in the range of 1 ½ - 2: 1 by volume |
A4.0: PRESTRESSED CONCRETE BEAMS
A4.0: PRESTRESSED CONCRETE BEAMS | ||||||
Description | Minimum Dimension (mm) of Concrete to give a Fire Resistance of:- | |||||
4 hrs | 3 hrs | 2 hrs | 1 ½ hrs | 1 hr | ½ hr | |
1 Siliceous aggregate concrete: | ||||||
(a) average concrete cover to tendons | 100* | 85* | 65* | 50* | 40 | 25 |
(b) beam width | 280 | 240 | 180 | 140 | 110 | 80 |
2. As (1) with vermiculite concrete slabs 15mm thick , used as permanent shuttering: | ||||||
(a) average concrete cover to tendons | 75* | 60 | 45 | 35 | 25 | 15 |
(b) beam width | 210 | 170 | 125 | 100 | 70 | 70 |
3. As (2) but with 25mm thick slabs: | ||||||
(a) average concrete cover to tendons | 65 | 50 | 35 | 25 | 15 | 15 |
(b) beam width | 180 | 140 | 100 | 70 | 60 | 60 |
4. As (1) with 15mm thick gypsum plaster with light mesh reinforcement: | ||||||
(a) average concrete cover to tendons | 90* | 75 | 50 | 40 | 30 | 15 |
(b) beam width | 250 | 210 | 170 | 110 | 85 | 70 |
5. As (1) with vermiculite/gypsum plaster+ 15m thick: | ||||||
(a) average concrete cover to tendons | 75* | 60 | 45 | 30 | 25 | 15 |
(b) beam width | 170 | 145 | 125 | 85 | 60 | 60 |
6. As (5) but with 25mm thick coating: | ||||||
(a) average concrete cover to tendons | 50 | 45 | 30 | 25 | 15 | 15 |
(b) beam width | 140 | 125 | 85 | 70 | 60 | 60 |
7. Lightweight aggregate concrete: | ||||||
(a) average concrete cover to tendons | 80 | 65 | 50 | 40 | 30 | 20 |
(b) beam width | 250 | 200 | 160 | 130 | 100 | 80 |
Note: * - Supplementary reinforcement, to hold the concrete cover in position, may be necessary + - Vermiculite/gypsum plaster should have a mix ratio in the range of 1 ½ - 2: 1 by volume |
A5.0: REINFORCED CONCRETE COLUMNS
A5.0: REINFORCED CONCRETE COLUMNS | ||||||
Description | Minimum Dimension (mm) of Concrete to give a Fire Resistance of:- | |||||
4 hrs | 3 hrs | 2 hrs | 1½ hrs | 1 hr | ½ hr | |
---|---|---|---|---|---|---|
A5.1 - All Face Exposed | ||||||
1. Siliceous aggregate concrete: | ||||||
(a) without additional protection | 450 | 400 | 300 | 250 | 200 | 150 |
(b) with cement or gypsum plaster 15mm thick on light mesh reinforcement | 300 | 275 | 225 | 150 | 150 | 150 |
(c) with vermiculite/ gypsum plaster* | 275 | 225 | 200 | 150 | 120 | 120 |
2. Limestone aggregate concrete or siliceous aggregate: | ||||||
(a) concrete with supplementary reinforcement in concrete cover | 300 | 275 | 225 | 200 | 190 | 150 |
3. Lightweight aggregate concrete | 300 | 275 | 225 | 200 | 150 | 150 |
A5.2 - One Face Exposed | ||||||
1. Siliceous aggregate concrete | ||||||
(a) without additional protection | 180 | 150 | 100 | 100 | 75 | 75 |
(b) with vermiculite/ gypsum plaster* 15mm thick on exposed faces | 125 | 100 | 75 | 75 | 65 | 65 |
Note: + - Vermiculite/gypsum plaster should have a mix ratio in the range of 1 ½ - 2: 1 by volume |
A6.0: STRUCTURAL STEEL
A6.0: STRUCTURAL STEEL | ||||||
A6.1 - Encased Steel Stanchions (Mass per metre not less than 45kg) | ||||||
Description | Minimum Thickness (mm) of Protection for a Fire Resistance of: | |||||
4 hrs | 3 hrs | 2 hrs | 1 ½ hrs | 1 hr | ½hr | |
A. Solid Protection* (Unplastered) | ||||||
1. Concrete not leaner than 1:2:4 mix with natural aggregates- | ||||||
(a) concrete not assumed to be load- bearing reinforced+ | 50 | - | 25 | 25 | 25 | 25 |
(b) concrete assumed to be load-bearing, reinforced in accordance with SS EN 1992 and SS EN 1994 | 75 | - | 50 | 50 | 50 | 50 |
2. Solid bricks of clay, composition or sand-lime | 100 | 75 | 50 | 50 | 50 | 50 |
3. Solid blocks of foamed slag or pumice concrete reinforced+ in every horizontal joint | 75 | 60 | 50 | 50 | 50 | 50 |
4. Sprayed vermiculite-cement | - | - | 38 | 32 | 19 | 12.5 |
B. Hollow Protection++ | ||||||
1. Solid bricks of clay, composition or sandlime reinforced in every horizontal joint, unplastered | 115 | - | 50 | 50 | 50 | 50 |
2. Solid blocks of foamed slag or pumice concrete reinforced+ in every horizontal joint, unplastered | 75 | - | 50 | 50 | 50 | 50 |
3. Metal lathing with gypsum or cement- lime plaster of thickness of - | - | - | 38§ | 25 | 19 | 12.5 |
4. Metal lathing:- | ||||||
(a) with vermiculite-gypsum or perlite-gypsum plaster of thickness of | 50§ | - | 19 | 16 | 12.5 | 12.5 |
(b) spaced 25mm from flanges with vermiculite-gypsum or perlite-gypsum plaster of thickness of | 44 | - | 19 | 12.5 | 12.5 | 12.5 |
5. Gypsum plasterboard with 1.6mm wire binding at 100mm pitch - | ||||||
(a) 9.5mm Plasterboard with gypsum plaster of thickness of | - | - | - | - | 12.5 | 12.5 |
(b) 19mm Plasterboard with gypsum plaster of thickness of | - | - | 12.5 | 10 | 7 | 7 |
6. Gypsum plasterboard with 1.6mm wire binding at 100mm pitch- | ||||||
(a) 9.5mm plasterboard with vermiculite-gypsum plaster of thickness of | - | - | 16 | 15 | 10 | 10 |
(b) 19mm plasterboard with vermiculite-gypsum plaster of thickness of | 38§ | - | 20 | 13 | 10 | 10 |
7. Vermiculite-cement slabs of 4:1 mix reinforced with wire mesh and finished with plaster skim. Slabs of thickness of | 63 | - | 25 | 25 | 25 | 25 |
Note: * - Solid protection means a casing which is bedded close to the steel without intervening cavities and with all joints in that casing made full and solid + - Reinforcement shall consist of steel binding wire not less than 2.3mm in thickness, or a steel mesh weighing not less than 0.48 kg/m2. In concrete protection, the spacing of that reinforcement shall not exceed 150mm in any direction ++ - Hollow protection means that there is a void between the protective material and the steel. All hollow protection to columns shall be effectively sealed at each floor level § - Light mesh reinforcement required 12.5mm to 19mm below surface unless special corner beads are used |
A6.2 - Encased Steel Beams (Mass per metre not less than 30kg)
A6.2 - Encased Steel Beams (Mass per metre not less than 30kg) | ||||||
Description | Minimum Thickness (mm) of Protection for a Fire Resistance of : | |||||
4 hrs | 3 hrs | 2 hrs | 1½ hrs | 1 hr | ½ hr | |
A. Solid Protection+ (Unplastered) | ||||||
1. Concrete not leaner than 1:2:4 mix with natural aggregates- | ||||||
(a) concrete not assumed to be load- bearing, reinforced++ | 75 | 50 | 25 | 25 | 25 | 25 |
(b) concrete assumed to be load-bearing, reinforced in accordance with SS EN 1992 and SS EN 1994 | 75 | 75 | 50 | 50 | 50 | 50 |
2. Sprayed vermiculite - cement | - | - | 38 | 32 | 19 | 12.5 |
B. Hollow Protection++ | ||||||
1. Metal lathing - | ||||||
(a) with cement-lime plaster of thickness of | - | - | 38 | 25 | 19 | 12.5 |
(b) with gypsum plaster of thickness of | - | - | 22 | 19 | 16 | 12.5 |
(c) with vermiculite-gypsum or perlite-gypsum plaster of thickness of | 32 | - | 12.5 | 12.5 | 12.5 | 12.5 |
2. Gypsum plasterboard with 1.6mm wire binding at 100mm pitch- | ||||||
(a) 9.5mm plasterboard with gypsum plaster of thickness of | - | - | - | - | 12.5 | 12.5 |
(b) 19 mm plasterboard with gypsum plaster of thickness of | - | - | 12.5 | 10 | 7 | 7 |
3. Plasterboard with 1.6mm wire at 100m pitch - | ||||||
(a) 9.5mm plaster nailed to wooden cradles finished with gypsum plaster of thickness of | - | - | - | - | - | 12.5 |
(b) 9.5mm plasterboard with vermiculite -gypsum plaster of thickness of | - | - | 16 | 15 | 10 | 10 |
(c) 19mm plasterboard with vermiculite-gypsum plaster of thickness of | 32 | - | 10 | 10 | 7 | 7 |
(d) 19mm plasterboard with gypsum plaster of thickness of | - | - | 20 | 13 | 10 | 10 |
4. Vermiculite-cement slabs of 4:1 mix reinforced with wire mesh and finished with plaster skim. Slabs of thickness of | 63 | - | 25 | 25 | 25 | 25 |
5. Gypsum-sand plaster 12.5mm thick applied to heavy duty (Type B as designated in EN 13168) Wood wool slabs of thickness of | - | - | 50 | 38 | 38 | 38 |
Note: * - Hollow protection means that there is a void between the protective materials and the steel. All hollow protection to columns shall be effectively sealed at each floor level + - Solid protection means a casing which is bedded close to the steel without intervening cavities and with all joints in that casing made full and solid ++ - Reinforcement shall consist of steel binding wire not less than 2.3mm in thickness, or a steel mesh weighing not less than 0.48 kg/m2. In concrete protection, the spacing of that reinforcement shall not exceed 150mm in any direction § - Light mesh reinforcement required 12.5mm to 19mm below surface unless special corner beads are used |
A7.0: STRUCTURAL ALUMINIUM
A7.0: STRUCTURAL ALUMINIUM | ||||||
Description | Minimum Thickness (mm) of Protection for a Fire Resistance of : | |||||
4 hrs | 3 hrs | 2 hrs | 1½ hrs | 1 hr | ½ hr | |
A7.1 - Solid Protection* | ||||||
1. Sprayed vermiculite-cement | - | - | - | - | 44 | 19 |
A7.2 - Hollow Protection+ | ||||||
1. Metal lathing with vermiculite-gypsum or perlite-gypsum plaster of thickness of | - | - | 32 | 22 | 16 | 12.5 |
2. Metal lathing finished with neat gypsum plaster of thickness of | - | - | - | - | 19 | 12.5 |
3. Gypsum plasterboard 19mm thick with 1.6 mm wire binding at 100mm pitch finished with gypsum-vermiculite plaster of thickness of | - | - | 22 | 16 | 10 | 10 |
Note: * - Solid protection means a casing which is bedded close to the alloy without intervening cavities and with all joints in that casing made full and solid + - Hollow protection means that there is a void between the protected material and the alloy. All hollow protection to columns shall be effectively sealed at each floor level |
A8.0: TIMBER FLOORS
A8.0: TIMBER FLOORS | ||||||||||||
Construction and materials | Minimum Thickness (mm) of Protection for a Fire Resistance of: | |||||||||||
1 hr | ½ hr | modified++ ½ hr | ||||||||||
1. Plain edge boarding on timber joists not less than 38mm wide with ceiling of - | ||||||||||||
(a) timber lath and plaster - thickness of plaster | - | 16 | 16 | |||||||||
(b) timber lath and plaster with plaster of minimum thickness of 16mm covered on underside with plasterboard of thickness | - | 12.5 | - | |||||||||
(c) metal lathing and plaster - thickness of plaster | ||||||||||||
(1) gypsum | - | 16 | - | |||||||||
(2) vermiculite | - | 12.5 | - | |||||||||
(d) one layer of plasterboard of thickness | - | - | 12.5 | |||||||||
(e) one layer of plasterboard of minimum thickness of 9.5mm finished with gypsum plaster of thickness | - | - | 12.5 | |||||||||
(f) one layer of plasterboards of minimum thickness of 12.5mm finished with gypsum plaster of thickness | - | 12.5 | - | |||||||||
(g) two layers of plasterboard of total thickness | - | 25 | 19 | |||||||||
(h) one layer of fibre insulating board of minimum thickness of 9.5mm finished with gypsum plaster of thickness | - | 5 | - | |||||||||
(i) one layer of fibre insulating board of minimum thickness of 12.5mm finished with gypsum plaster of thickness | - | - | 12.5 | |||||||||
(j) wood wool slab 25mm thick finished with gypsum plaster of thickness | - | 5 | - | |||||||||
2. Tongued and grooved boarding of not less than 16mm (finished) thickness* on timber joists not less than 38 mm wide ceiling of - | ||||||||||||
(a) timber lath and plaster - thickness of plaster | - | - | 16 | |||||||||
(b) timber lath and plaster with plaster of minimum thickness of 16mm covered on underside with plasterboard of thickness | - | 9.5 | - | |||||||||
(c) metal lathing and plaster - thickness of plaster | ||||||||||||
(1) gypsum | 22 | 16 | - | |||||||||
(2) vermiculite | 12.5 | 12.5 | - | |||||||||
(d) one layer of plasterboard of thickness | - | - | 9.5 | |||||||||
(e) one layer of plasterboard of minimum thickness of 9.5mm finished with- | ||||||||||||
(1) gypsum plaster of thickness | - | 12.5 | - | |||||||||
(2) vermiculite-gypsum plaster of thickness | 12.5 | - | - | |||||||||
(f) one layer of plasterboards of minimum thickness of 12.5mm finished with gypsum plaster of thickness | - | 5 | - | |||||||||
(g) two layers of plasterboard of total thickness | - | 22 | - | |||||||||
(h) one layer of fibre insulating board of minimum thickness of 9.5mm finished with gypsum plaster of thickness | - | - | 5 | |||||||||
(i) wood wool slab 25mm thick finished with - | ||||||||||||
(1) gypsum plaster of thickness | - | 5 | - | |||||||||
(2) vermiculite - gypsum plaster of thickness | 10 | - | - | |||||||||
3. Tongued and grooved boardings of not less than 21mm (finished) thickness* on timber joists not less than | ||||||||||||
(a) timber lath and plaster - thickness of plaster | - | 16 | - | |||||||||
(b) metal lathing and plaster - thickness of plaster | - | 16 | - | |||||||||
(c) one layer of plasterboard of thickness | - | - | 9.5 | |||||||||
(d) one layer of plasterboard of minimum thickness of 9.5mm finished with - | ||||||||||||
(1) gypsum plaster of thickness | - | 12.5 | - | |||||||||
(2) vermiculite-gypsum plaster of thickness | 12.5 | - | - | |||||||||
(e) one layer of plasterboard of minimum thickness of 12.5mm finished with gypsum plaster of thickness | - | 5 | - | |||||||||
(f) two layers of plasterboard of total thickness | - | 19 | - | |||||||||
(g) one layer of fibre insulating board of thickness | - | - | 12.5 | |||||||||
(h) one layer of fibre insulating board of minimum thickness of 12.5mm finished with gypsum plaster of thickness | - | 12.5 | - | |||||||||
(i) wood wool slab 25mm thick finished with - | ||||||||||||
(1) gypsum plaster of thickness | - | 5 | - | |||||||||
(2) vermiculite-gypsum plaster of thickness | 10 | - | - | |||||||||
Note: * - Or an equivalent thickness of wood chipboard ++ - The term “modified ½ hour” refers to the requirements specified in item 3(a) of Table 3.4A |
A9.0: REINFORCED CONCRETE FLOORS (SILICEOUS OR CALCAREOUS AGGREGATE)
A9.0: REINFORCED CONCRETE FLOORS (SILICEOUS OR CALCAREOUS AGGREGATE) | ||||||||
Floor Construction | Minimum Dimension (mm) to give Fire Resistance of : | |||||||
4 hrs | 3 hrs | 2 hrs | 1 ½ hrs | 1 hr | ½ hr | |||
Solid slab | Average cover to reinforcement | 25 | 25 | 20 | 20 | 15 | 15 | |
Depth, overall+ | 150 | 150 | 125 | 125 | 100 | 100 | ||
Cored slabs in which the cores are circular or are higher than wide. Not less than 50% of the gross across section of the floor should be solid material | Average cover to reinforcement | 25 | 25 | 20 | 20 | 15 | 15 | |
Thickness under cores | 50 | 40 | 40 | 30 | 25 | 20 | ||
Depth, overall+ | 190 | 175 | 160 | 140 | 110 | 100 | ||
Hollow box section with one or more longitudinal cavities which are wider than high | Average cover to reinforcement | 25 | 25 | 20 | 20 | 15 | 15 | |
Thickness of bottom flange | 50 | 40 | 40 | 30 | 25 | 20 | ||
Depth, overall+ | 230 | 205 | 180 | 155 | 130 | 105 | ||
Ribbed floor with hollow infill blocks of clay, or inverted T-section beams with hollow infill blocks of concrete or clay. A floor in which less than 50% of the gross cross section is solid material must be provided with a 15mm plaster coating on soffit | Average cover to reinforcement | 25 | 25 | 20 | 20 | 15 | 15 | |
Width or rib, or beam, at soffit | 125 | 100 | 90 | 80 | 70 | 50 | ||
Depth, overall+ | 190 | 175 | 160 | 140 | 110 | 100 | ||
Upright T-section | Average bottom cover to reinforcement | 65* | 55* | 45* | 35 | 25 | 15 | |
Side cover to reinforcement | 65 | 55 | 45 | 35 | 25 | 15 | ||
Least width or down-standing leg | 150 | 140 | 115 | 90 | 75 | 60 | ||
Thickness of flange+ | 150 | 150 | 125 | 125 | 100 | 90 | ||
Inverted channel sections with radius at intersection of soffits with top of leg not exceeding depth of section | Average bottom cover to reinforcement | 65* | 55* | 45* | 35 | 25 | 15 | |
Side cover to reinforcement | 40 | 30 | 25 | 20 | 15 | 10 | ||
Least width or down-standing leg | 75 | 70 | 60 | 45 | 40 | 30 | ||
Thickness at crown+ | 150 | 150 | 125 | 125 | 100 | 90 | ||
Inverted channel sections or U-sections with radius at intersection of soffits with top of leg exceeding depth of section | Average bottom cover to reinforcement | 65* | 55* | 45* | 35 | 25 | 15 | |
Side cover to reinforcement | 40 | 30 | 25 | 20 | 15 | 10 | ||
Least width or down-standing leg | 70 | 60 | 50 | 40 | 35 | 25 | ||
Thickness at crown+ | 150 | 150 | 100 | 100 | 75 | 65 | ||
Note: * - Supplementary reinforcement, to hold the concrete cover in position, may be necessary + - Non-combustible screeds and finishes may be included in these dimensions |
A10.0: PRESTRESSED CONCRETE FLOORS (SILICEOUS OR CALCAREOUS AGGREGATE)
A10.0: PRESTRESSED CONCRETE FLOORS (SILICEOUS OR CALCAREOUS AGGREGATE) | |||||||
Floor Construction | Minimum Dimension (mm) to give Fire Resistance of : | ||||||
4 hrs | 3 hrs | 2 hrs | 1 ½ hrs | 1 hr | ½ hr | ||
Solid slab | Average cover to reinforcement | 65* | 50* | 40 | 30 | 25 | 15 |
Depth, overall+ | 150 | 150 | 125 | 125 | 100 | 90 | |
Cored slabs in which the cores are circular or are higher than wide. Not less than 50% of the gross across section of the floor should be solid material | Average cover to reinforcement | 65* | 50* | 40 | 30 | 25 | 15 |
Thickness under cores | 50 | 40 | 40 | 30 | 25 | 20 | |
Depth, overall+ | 190 | 175 | 160 | 140 | 110 | 100 | |
Hollow box section with one or more longitudinal cavities which are wider than high | Average cover to reinforcement | 65* | 50* | 40 | 30 | 25 | 15 |
Thickness of bottom flange | 65 | 50 | 40 | 30 | 25 | 25 | |
Depth, overall+ | 230 | 205 | 180 | 155 | 130 | 105 | |
Ribbed floor with hollow infill blocks of clay, or inverted T-section beams with hollow infill blocks of concrete or clay. A floor in which less than 50% of the gross cross section is solid material must be provided with a 15mm plaster coating on soffit | Average cover to reinforcement | 65* | 50* | 40 | 30 | 25 | 15 |
Width or rib, or beam, at soffit | 125 | 100 | 90 | 80 | 70 | 50 | |
Depth, overall+ | 190 | 175 | 160 | 140 | 110 | 100 | |
Upright T-section | Average bottom cover to reinforcement | 100* | 85* | 65* | 50* | 40 | 25 |
Side cover to reinforcement | 100 | 85 | 65 | 50 | 40 | 25 | |
Least width or down-standing leg | 250 | 200 | 150 | 110 | 90 | 60 | |
Thickness of flange+ | 150 | 150 | 125 | 125 | 100 | 90 | |
Inverted channel sections with radius at intersection of soffits with top of leg not exceeding depth of section | Average bottom cover to reinforcement | 100* | 85* | 65* | 50* | 40 | 25 |
Side cover to reinforcement | 50 | 45 | 35 | 25 | 20 | 10 | |
Least width or down-standing leg | 125 | 100 | 75 | 55 | 45 | 30 | |
Thickness at crown+ | 150 | 150 | 125 | 125 | 100 | 90 | |
Inverted channel sections or U-sections with radius at intersection of soffits with top of leg exceeding depth of section | Average bottom cover to reinforcement | 100* | 85* | 65* | 50* | 40 | 25 |
Side cover to reinforcement | 50 | 45 | 35 | 25 | 20 | 15 | |
Least width or down-standing leg | 110 | 90 | 70 | 50 | 45 | 30 | |
Thickness at crown+ | 150 | 150 | 125 | 125 | 100 | 90 | |
Note: * - Supplementary reinforcement, to hold the concrete cover in position, may be necessary + - Non-combustible screeds and finishes may be included in these dimensions |
A11.0: GLAZING
A11.0: GLAZING | ||
Construction and materials | Minimum Thickness (mm) of Glazing for a Period of:- | |
1 hr | ½ hr | |
1. Glass, in direct combination with metal, the melting point of which is not lower than 982.2°C, in square not exceeding 0.015m2 in area | ||
Thickness of glass | - | 6.35 |
2. Glass reinforced with wire not less than 0.46mm in diameter laid to a square mesh measuring 12.70mm from centre to centre of wire, and electrically welded at the intersections, or laid to a hexagonal mesh measuring 25.40mm across the flat side | ||
Thickness of glass | - | 6.35 |
In windows, doors , borrowed lights, lanterns and skylights, glass complying with paragraphs 1 or 2 of this Table shall be fixed with wood or metal beads or with a glazing compound in conjunction with sprigs or clips in panels not exceeding 0.372m 2 in area in timber frames (fixed shut) having a minimum width and thickness of 44.45mm clear of rebates | ||
3. Glass reinforced with wire as in paragraph 2 of this Table, in windows, doors, borrowed lights, lanterns and skylights, fixed with metal beads in panels not exceeding 1.115m2 in metal frames (fixed shut) all metal having a melting point not lower than 982.2oC, the thickness of glass | 6.35 | 6.35 |
4. Glass bricks or blocks in walls | ||
Laid in cement / lime / sand mortar with light wire reinforcing mesh in every third horizontal joint in a panel not exceeding 2.438m in width or height set along the sides and head into recesses in the surrounding non-combustible construction. The depth of such recessed shall be not less than 25.40mm, the glass blocks extending into the recesses to a depth of 12.70mm and bedded upon layer of glass fibre. A non-hardening mastic shall be used to fill the spaces between the sides of the recesses and the faces of the panels | - | 98.43 |
Note: In this Table the absence of a figure in a period column indicated that glazing described is not acceptable for the period applicable to that column |
Updated 2 Sep 2024